girgit.org

Alternating Current

Power in an ac circuit: the power factor

The big ideaIn an ac circuit the average power is \( P = VI\cos\phi \): only the part of the current that is in step with the voltage does any work, and \( \cos\phi \) is the power factor.

In simple words

Imagine pulling a cart with a rope. If you pull straight ahead, all your effort moves the cart. If you pull partly sideways, some of your effort is wasted. In an ac circuit, the flow and the push can be out of step. The part of the flow that keeps step with the push does the real work. The part that is out of step just sloshes energy back and forth and does nothing useful, though it still has to travel along the wires.

Average power in a series LCR circuit

A source \( v = v_m\sin\omega t \) drives a current \( i = i_m\sin(\omega t + \phi) \), with \( i_m = v_m/Z \) and \( \phi = \tan^{-1}\left(\dfrac{X_C - X_L}{R}\right) \). The instantaneous power from the source is

\[ p = vi = v_m i_m\sin\omega t\,\sin(\omega t + \phi) = \frac{v_m i_m}{2}\left[\cos\phi - \cos(2\omega t + \phi)\right] \]

The second term swings above and below zero and averages to zero over a cycle. Only the first, steady term is left:

\[ P = \frac{v_m i_m}{2}\cos\phi = \frac{v_m}{\sqrt{2}}\,\frac{i_m}{\sqrt{2}}\cos\phi = VI\cos\phi \]

Since \( V = IZ \), this can also be written \( P = I^2Z\cos\phi \). The factor \( \cos\phi \) is the power factor. From the impedance triangle, \( \cos\phi = R/Z \).

Four cases

CircuitPhase \( \phi \)Power factorAverage power
(i) Pure resistor01Largest: \( VI \)
(ii) Pure inductor or pure capacitor\( \pm\pi/2 \)0Zero, though current flows
(iii) RL, RC or LCRBetweenBetween 0 and 1\( VI\cos\phi \), all used up in \( R \)
(iv) LCR at resonance01Largest: \( I^2R \)

In case (ii) a current flows but no power is used. Such a current is called a wattless current. In every case, the only part of an ac circuit that actually uses up energy is its resistance; ideal coils and capacitors only store energy and give it back.

Worked example

For the circuit worked out in "The series LCR circuit" (230 V, \( R = 30\ \Omega \), \( Z = 50\ \Omega \), \( I = 4.6 \) A), find the power factor and the power used.

  1. \( \cos\phi = R/Z = 30/50 = \) 0.6.
  2. \( P = VI\cos\phi = 230 \times 4.6 \times 0.6 = \) 635 W.
  3. Check: \( I^2R = 4.6^2 \times 30 = 21.16 \times 30 = 635 \) W. All of it is used in the resistor.

Power and wattless components

Think of the current phasor \( \mathbf{I} \), lagging the voltage by \( \phi \), as two pieces at right angles:

  • \( I_P = I\cos\phi \), along the voltage: the power component, which does the work.
  • \( I_q = I\sin\phi \), at right angles to the voltage: the wattless component, which uses no power.

Try it: switch loads on a home's meter board and watch the old meter's disc. It turns only for the part of the current in step with the voltage.

Why a low power factor is costly

To deliver a fixed power \( P \) at a fixed voltage, \( I = P/(V\cos\phi) \). A small \( \cos\phi \) means a bigger current, and a bigger current wastes more energy as \( I^2R \) heat in the long transmission wires. Motors in factories and pumps are coils, so they make the current lag and drag the power factor down.

Try it: guess first, then add a capacitor across the pump and watch the line current.

The cure: connect a capacitor in parallel with the load. The capacitor draws a current that leads the voltage, a leading wattless current. Choose it the right size and it cancels the lagging wattless current \( I_q \). What is left is just \( I_P \), in phase with the voltage, so the power factor is close to 1 and the line carries only the current that does useful work.

Try it

A water pump on 230 V draws 10 A at a power factor of 0.6. Find the power it uses and the current the line would need to carry if the power factor were raised to 1.

Answer
\( P = 230 \times 10 \times 0.6 = \) 1380 W. The power component is \( 10 \times 0.6 = 6 \) A and the wattless component \( 10 \times 0.8 = 8 \) A. At power factor 1, the same 1380 W needs only 6 A.

Don't mix these up

  • \( P = VI \) is right only for a pure resistor (or at resonance). In general \( P = VI\cos\phi \).
  • \( \cos\phi = R/Z \), not \( R/X \) or \( X/Z \).
  • A wattless current is a real current: it heats the supply wires, even though the load uses no power from it.

Words to know

Power factor
\( \cos\phi \): the share of \( VI \) that is real, used-up power.
Wattless current
Current 90° out of phase with the voltage; it carries no average power.
Power component
\( I\cos\phi \), the part of the current in phase with the voltage.
Wattless component
\( I\sin\phi \), the part at right angles to the voltage.
Average power
\( P = VI\cos\phi = I^2R \) in an ac circuit.

The rms voltages across R, C and L in a series circuit are 60 V, 50 V and 130 V. The power factor is

  1. 0.5
  2. 0.6
  3. 1.0

A pure capacitor carries an rms current of 2 A on 230 V mains. The average power it uses is

  1. 460 W
  2. 230 W
  3. zero

A factory's motors give it a lagging power factor of 0.7. To raise it towards 1, the factory should connect

  1. an inductor in series
  2. a capacitor in parallel
  3. a large resistor in series